{"id":6169,"date":"2015-05-26T08:25:29","date_gmt":"2015-05-26T07:25:29","guid":{"rendered":"https:\/\/blog.wika.com\/en\/?p=6169"},"modified":"2021-12-02T08:37:43","modified_gmt":"2021-12-02T07:37:43","slug":"connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor","status":"publish","type":"post","link":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/","title":{"rendered":"Connection of an Ex nA digital indicator to an Ex i sensor"},"content":{"rendered":"<p><strong>Is it possible to connect a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Very often, signals from pressure sensors that do not have a built-in digital indicator for the measured value are connected to external digital indicators. These digital indicators enable an on-site display of the measured value and, thus, a convenient and immediate reading of, for example, the level in storage vessels.<\/strong><\/p>\n<p>Pressure sensors for hazardous areas are frequently designed with the ignition protection type \u201cintrinsically safe\u201d, since this allows interventions in an active electrical circuit and less energy is needed. However, this also means that there is insufficient energy available for a powerful measured value display. As a result, digital indicators are often designed with ignition protection types that enable more current and voltage to be allowed. Frequently, digital indicators are designed as \u201cnon-incendive\u201d (Ex nA). This ignition protection type enables power-hungry instruments to be operated in Ex areas too. However, Ex nA is limited for use in zone 2 &#8211; so in areas in which an explosive atmosphere only rarely occurs.<\/p>\n<h2>The right connection of digital indicator and barrier<\/h2>\n\n      <div class=\"wp-caption alignright\" style=\"max-width:396px;\"><a href=\"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital2.jpg\"><img decoding=\"async\" src=\"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital2-388x218.jpg\" alt=\"Nicht zul\u00e4ssige Verschaltung eines Ex i Drucksensors mit Trennbarriere und Ex nA Digitalanzeige\" \/><\/a><p class=\"wp-caption-text\">Non-permissible connection of an Ex i pressure sensor with isolated barrier and Ex nA digital indicator.<\/p><\/div>\n    \n<p>Every Ex i sensor requires an intrinsically safe barrier for its voltage supply, so that the interconnection is considered as intrinsically safe and the benefits, such as maintenance work without the need for a fire certificate, can be used. Digital indicators are frequently integrated as passive element, with or without an external power supply, directly in the 4 &#8230; 20 mA current signal of a sensor. Since an Ex nA digital indicator has no Ex i performance data in its approval, it cannot therefore be used in a \u201cProof of intrinsic safety\u201d. Therefore, an Ex nA indicator cannot be connected in an Ex i circuit.<\/p>\n\n      <div class=\"wp-caption alignleft\" style=\"max-width:396px;\"><a href=\"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg\"><img decoding=\"async\" src=\"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital-388x218.jpg\" alt=\"Text missing\" \/><\/a><p class=\"wp-caption-text\">Correct connection\u00a0of an Ex i pressure sensor with isolated barrier and Ex nA digital indicator.<\/p><\/div>\n    \n<p>There is, however, the possibility to connect a digital indicator with an Ex i pressure sensor in zone 2. The prerequisite is that the intrinsically safe isolated barrier also possesses an Ex nA approval and must be installed in zone 2.<\/p>\n<p>&nbsp;<\/p>\n<p>&nbsp;<\/p>\n<p>&nbsp;<\/p>\n<p>&nbsp;<\/p>\n<p><strong>Read also our articles<\/strong><br \/>\n<a href=\"https:\/\/blog.wika.com\/en\/knowhow\/barrier-intrinsically-safe-pressure-sensors-inseparable-pair\/\">Ex barrier and intrinsically safe pressure sensors \u2013 an inseparable pair<br \/>\n<\/a><a href=\"https:\/\/blog.wika.com\/en\/knowhow\/proof-intrinsic-safety-atex-approved-pressure-sensor\/\">Proof of intrinsic safety for an ATEX-approved pressure sensor<\/a><\/p>\n<p><strong>Note<br \/>\n<\/strong>Should you need any help with choosing a suitable solution for your pressure measurement requirement, your <a href=\"https:\/\/www.wika.com\/en-en\/contact.WIKA\" target=\"_blank\" rel=\"noopener noreferrer external\">contact person <\/a>will gladly be of assistance.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Is it possible to connect a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Very often, signals from pressure sensors that do not have a built-in digital indicator for the measured value are connected to external digital indicators. These digital indicators enable an on-site display of the measured [&hellip;]<\/p>\n","protected":false},"author":16,"featured_media":6209,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[5],"tags":[254,260,77],"class_list":["post-6169","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-knowhow","tag-ex-protection","tag-indication","tag-pressure-sensor"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.2 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Connection of an Ex nA digital indicator to an Ex i sensor<\/title>\n<meta name=\"description\" content=\"Is it possible to connect a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Very often, signals from\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/\" \/>\n<meta property=\"og:locale\" content=\"en_GB\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Connection of an Ex nA digital indicator to an Ex i sensor\" \/>\n<meta property=\"og:description\" content=\"Is it possible to connect a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Very often, signals from\" \/>\n<meta property=\"og:url\" content=\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/\" \/>\n<meta property=\"og:site_name\" content=\"WIKA blog\" \/>\n<meta property=\"og:image\" content=\"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"838\" \/>\n\t<meta property=\"og:image:height\" content=\"471\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"Stefan Heusel\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Stefan Heusel\" \/>\n\t<meta name=\"twitter:label2\" content=\"Estimated reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"3 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/\"},\"author\":{\"name\":\"Stefan Heusel\",\"@id\":\"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343\"},\"headline\":\"Connection of an Ex nA digital indicator to an Ex i sensor\",\"datePublished\":\"2015-05-26T07:25:29+00:00\",\"dateModified\":\"2021-12-02T07:37:43+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/\"},\"wordCount\":439,\"commentCount\":0,\"image\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg\",\"keywords\":[\"Ex protection\",\"Indication\",\"Pressure sensor\"],\"articleSection\":[\"Know-how\"],\"inLanguage\":\"en-GB\"},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/\",\"url\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/\",\"name\":\"Connection of an Ex nA digital indicator to an Ex i sensor\",\"isPartOf\":{\"@id\":\"https:\/\/blog.wika.com\/en\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg\",\"datePublished\":\"2015-05-26T07:25:29+00:00\",\"dateModified\":\"2021-12-02T07:37:43+00:00\",\"author\":{\"@id\":\"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343\"},\"description\":\"Is it possible to connect a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Very often, signals from\",\"breadcrumb\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#breadcrumb\"},\"inLanguage\":\"en-GB\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#primaryimage\",\"url\":\"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg\",\"contentUrl\":\"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg\",\"width\":838,\"height\":471,\"caption\":\"correct connection Ex nA\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\/\/blog.wika.com\/en\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Connection of an Ex nA digital indicator to an Ex i sensor\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/blog.wika.com\/en\/#website\",\"url\":\"https:\/\/blog.wika.com\/en\/\",\"name\":\"WIKA blog\",\"description\":\"Our blog offers many interesting articles on pressure, temperature, level, force, flow measurement calibration technology and provides insights into the WIKA Group.\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/blog.wika.com\/en\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-GB\"},{\"@type\":\"Person\",\"@id\":\"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343\",\"name\":\"Stefan Heusel\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png\",\"url\":\"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png\",\"contentUrl\":\"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png\",\"caption\":\"Stefan Heusel\"},\"url\":\"https:\/\/blog.wika.com\/en\/author\/snhl\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Connection of an Ex nA digital indicator to an Ex i sensor","description":"Is it possible to connect a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Very often, signals from","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/","og_locale":"en_GB","og_type":"article","og_title":"Connection of an Ex nA digital indicator to an Ex i sensor","og_description":"Is it possible to connect a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Very often, signals from","og_url":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/","og_site_name":"WIKA blog","og_image":[{"width":838,"height":471,"url":"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg","type":"image\/jpeg"}],"author":"Stefan Heusel","twitter_misc":{"Written by":"Stefan Heusel","Estimated reading time":"3 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#article","isPartOf":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/"},"author":{"name":"Stefan Heusel","@id":"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343"},"headline":"Connection of an Ex nA digital indicator to an Ex i sensor","datePublished":"2015-05-26T07:25:29+00:00","dateModified":"2021-12-02T07:37:43+00:00","mainEntityOfPage":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/"},"wordCount":439,"commentCount":0,"image":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#primaryimage"},"thumbnailUrl":"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg","keywords":["Ex protection","Indication","Pressure sensor"],"articleSection":["Know-how"],"inLanguage":"en-GB"},{"@type":"WebPage","@id":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/","url":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/","name":"Connection of an Ex nA digital indicator to an Ex i sensor","isPartOf":{"@id":"https:\/\/blog.wika.com\/en\/#website"},"primaryImageOfPage":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#primaryimage"},"image":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#primaryimage"},"thumbnailUrl":"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg","datePublished":"2015-05-26T07:25:29+00:00","dateModified":"2021-12-02T07:37:43+00:00","author":{"@id":"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343"},"description":"Is it possible to connect a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Very often, signals from","breadcrumb":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#breadcrumb"},"inLanguage":"en-GB","potentialAction":[{"@type":"ReadAction","target":["https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/"]}]},{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#primaryimage","url":"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg","contentUrl":"https:\/\/blog.wika.com\/en\/files\/2015\/05\/Connection_EX_na_digital.jpg","width":838,"height":471,"caption":"correct connection Ex nA"},{"@type":"BreadcrumbList","@id":"https:\/\/blog.wika.com\/en\/knowhow\/connection-of-an-ex-na-digital-indicator-to-an-ex-i-sensor\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/blog.wika.com\/en\/"},{"@type":"ListItem","position":2,"name":"Connection of an Ex nA digital indicator to an Ex i sensor"}]},{"@type":"WebSite","@id":"https:\/\/blog.wika.com\/en\/#website","url":"https:\/\/blog.wika.com\/en\/","name":"WIKA blog","description":"Our blog offers many interesting articles on pressure, temperature, level, force, flow measurement calibration technology and provides insights into the WIKA Group.","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/blog.wika.com\/en\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-GB"},{"@type":"Person","@id":"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343","name":"Stefan Heusel","image":{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png","url":"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png","contentUrl":"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png","caption":"Stefan Heusel"},"url":"https:\/\/blog.wika.com\/en\/author\/snhl\/"}]}},"_links":{"self":[{"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/posts\/6169","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/users\/16"}],"replies":[{"embeddable":true,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/comments?post=6169"}],"version-history":[{"count":9,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/posts\/6169\/revisions"}],"predecessor-version":[{"id":12389,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/posts\/6169\/revisions\/12389"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/media\/6209"}],"wp:attachment":[{"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/media?parent=6169"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/categories?post=6169"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/tags?post=6169"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}