{"id":6924,"date":"2016-03-31T10:00:10","date_gmt":"2016-03-31T08:00:10","guid":{"rendered":"https:\/\/blog.wika.com\/en\/?p=6924"},"modified":"2021-10-11T10:05:39","modified_gmt":"2021-10-11T08:05:39","slug":"integration-of-pressure-sensors-into-the-plc","status":"publish","type":"post","link":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/","title":{"rendered":"Integration of pressure sensors into the PLC"},"content":{"rendered":"<p><strong>The construction of a traditional current loop for the capture of pressure sensor signals has its pitfalls \u2013 especially when not only a signal must be transmitted to the PLC, but also a local indicator has to be integrated. Let&#8217;s have a look at the example of a pressure sensor with the output signal that is most commonly used in industry, 4 \u2026 20 mA, and its connection to a PLC.<\/strong><\/p>\n<p>Again and again, in the design of current loops confusion arises, since in day-to-day implementation basic technical facts are no longer automatically known. Here&#8217;s an example: When connecting sensors to the PLC, a \u201csingle-wire design\u201d is frequently used. With this, a 3-wire sensor is connected to an external power supply unit and then connected to the PLC with an additional wire. However, this system only works on condition that both parts are connected to the same power supply \u2013 an important detail which is often forgotten. This becomes evident if a 2-wire sensor should be connected with a 4 \u2026 20 mA output: Three wires are available, but the pressure sensor only offers two connections. Here, the clear assignment and cabling of current and signal wiring is not always simple (see also the main picture: \u201cSingle-wire design\u201d: Correct connection of 3- and 2-wire pressure sensors).<\/p>\n<h2>Additional Integration of a local indicator into the PLC<\/h2>\n\n      <div class=\"wp-caption alignright\" style=\"max-width:396px;\"><img decoding=\"async\" src=\"https:\/\/blog.wika.com\/en\/files\/2016\/03\/skizze-2-gb-388x216.jpg\" alt=\"Integration of pressure sensors into the PLC\" \/><p class=\"wp-caption-text\">Integration of pressure sensors into the PLC<\/p><\/div>\n    \n<p>The complexity increases when a local digital indicator for the measured value is to be integrated into the circuit, in the given example, a 2-wire instrument. As is generally understood, a pressure sensor converts the measured pressure into a current value, which is normally transmitted with 0 bar as 4 mA and the maximum of the measuring range as 20 mA. The intermediate values are proportional. In order that the measured value can be read locally, the digital indicator required for this \u2013 in the simplest case \u2013 is integrated directly into the current loop and also powered via this.<\/p>\n<p>Since the digital indicator and the pressure sensor are connected in the circuit in series, it must be checked that the PLC can provide enough energy. Depending on the manufacturer, the information is hidden behind a variety of terms found in the data sheets for the individual components. Users must strictly check these functional data for compatibility so that sensor, indicator and automatic signal processing within the PLC actually fulfil their function. Due to the series connection of the circuit, and the 4 \u2026 20 mA signal selected in the example, the voltage of the PLC at 20 mA must equal the sum of the two minimum operating voltages of sensor and indicator. Only then can the signal also utilise the full range of 4 \u2026 20 mA. A PLC voltage that is too low would first be seen on a rise in pressure: Even at the highest pressure, 20 mA would not be reached, and so a system pressure of 100 bar, for example, would be shown as a maximum of 85 bar.<\/p>\n<p>Some manufacturers have recognised this complexity and therefore additionally specify the \u201cload\u201d (i.e. the resistance) that their instrument represents. The current loop works properly when the sum of the resistances of the sensor and indicator is smaller than the maximum load at the PLC input Card.<\/p>\n<p><strong>Note<br \/>\n<\/strong>Further information on electronic <a href=\"https:\/\/www.wika.com\/en-en\/pressure_sensors.WIKA\" rel=\"external\" target=\"_blank\">pressure sensors<\/a> and <a href=\"https:\/\/www.wika.com\/en-en\/pressure_switches.WIKA?36543=36543_1\" rel=\"external\" target=\"_blank\">electronic pressure switches<\/a> can be found on the WIKA website. Should you need any help with choosing a suitable switching solution for your pressure, temperature or level measurement requirement, your <a href=\"https:\/\/www.wika.com\/en-en\/contact.WIKA\" rel=\"external\" target=\"_blank\">contact person<\/a> will gladly be of assistance.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>The construction of a traditional current loop for the capture of pressure sensor signals has its pitfalls \u2013 especially when not only a signal must be transmitted to the PLC, but also a local indicator has to be integrated. Let&#8217;s have a look at the example of a pressure sensor with the output signal that [&hellip;]<\/p>\n","protected":false},"author":16,"featured_media":7043,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[5],"tags":[260,77],"class_list":["post-6924","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-knowhow","tag-indication","tag-pressure-sensor"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.2 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Integration of pressure sensors into the PLC - WIKA blog<\/title>\n<meta name=\"description\" content=\"The construction of a traditional current loop for the capture of pressure sensor signals has its pitfalls.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/\" \/>\n<meta property=\"og:locale\" content=\"en_GB\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Integration of pressure sensors into the PLC - WIKA blog\" \/>\n<meta property=\"og:description\" content=\"The construction of a traditional current loop for the capture of pressure sensor signals has its pitfalls.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/\" \/>\n<meta property=\"og:site_name\" content=\"WIKA blog\" \/>\n<meta property=\"og:image\" content=\"https:\/\/blog.wika.com\/en\/files\/2016\/04\/plc.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"838\" \/>\n\t<meta property=\"og:image:height\" content=\"471\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"Stefan Heusel\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Stefan Heusel\" \/>\n\t<meta name=\"twitter:label2\" content=\"Estimated reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"3 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/\"},\"author\":{\"name\":\"Stefan Heusel\",\"@id\":\"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343\"},\"headline\":\"Integration of pressure sensors into the PLC\",\"datePublished\":\"2016-03-31T08:00:10+00:00\",\"dateModified\":\"2021-10-11T08:05:39+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/\"},\"wordCount\":591,\"commentCount\":0,\"image\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/blog.wika.com\/en\/files\/2016\/04\/plc.jpg\",\"keywords\":[\"Indication\",\"Pressure sensor\"],\"articleSection\":[\"Know-how\"],\"inLanguage\":\"en-GB\"},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/\",\"url\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/\",\"name\":\"Integration of pressure sensors into the PLC - WIKA blog\",\"isPartOf\":{\"@id\":\"https:\/\/blog.wika.com\/en\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/blog.wika.com\/en\/files\/2016\/04\/plc.jpg\",\"datePublished\":\"2016-03-31T08:00:10+00:00\",\"dateModified\":\"2021-10-11T08:05:39+00:00\",\"author\":{\"@id\":\"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343\"},\"description\":\"The construction of a traditional current loop for the capture of pressure sensor signals has its pitfalls.\",\"breadcrumb\":{\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#breadcrumb\"},\"inLanguage\":\"en-GB\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#primaryimage\",\"url\":\"https:\/\/blog.wika.com\/en\/files\/2016\/04\/plc.jpg\",\"contentUrl\":\"https:\/\/blog.wika.com\/en\/files\/2016\/04\/plc.jpg\",\"width\":838,\"height\":471,\"caption\":\"Integration of pressure sensors into the PLC\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\/\/blog.wika.com\/en\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Integration of pressure sensors into the PLC\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/blog.wika.com\/en\/#website\",\"url\":\"https:\/\/blog.wika.com\/en\/\",\"name\":\"WIKA blog\",\"description\":\"Our blog offers many interesting articles on pressure, temperature, level, force, flow measurement calibration technology and provides insights into the WIKA Group.\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/blog.wika.com\/en\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-GB\"},{\"@type\":\"Person\",\"@id\":\"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343\",\"name\":\"Stefan Heusel\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png\",\"url\":\"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png\",\"contentUrl\":\"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png\",\"caption\":\"Stefan Heusel\"},\"url\":\"https:\/\/blog.wika.com\/en\/author\/snhl\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Integration of pressure sensors into the PLC - WIKA blog","description":"The construction of a traditional current loop for the capture of pressure sensor signals has its pitfalls.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/","og_locale":"en_GB","og_type":"article","og_title":"Integration of pressure sensors into the PLC - WIKA blog","og_description":"The construction of a traditional current loop for the capture of pressure sensor signals has its pitfalls.","og_url":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/","og_site_name":"WIKA blog","og_image":[{"width":838,"height":471,"url":"https:\/\/blog.wika.com\/en\/files\/2016\/04\/plc.jpg","type":"image\/jpeg"}],"author":"Stefan Heusel","twitter_misc":{"Written by":"Stefan Heusel","Estimated reading time":"3 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#article","isPartOf":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/"},"author":{"name":"Stefan Heusel","@id":"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343"},"headline":"Integration of pressure sensors into the PLC","datePublished":"2016-03-31T08:00:10+00:00","dateModified":"2021-10-11T08:05:39+00:00","mainEntityOfPage":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/"},"wordCount":591,"commentCount":0,"image":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#primaryimage"},"thumbnailUrl":"https:\/\/blog.wika.com\/en\/files\/2016\/04\/plc.jpg","keywords":["Indication","Pressure sensor"],"articleSection":["Know-how"],"inLanguage":"en-GB"},{"@type":"WebPage","@id":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/","url":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/","name":"Integration of pressure sensors into the PLC - WIKA blog","isPartOf":{"@id":"https:\/\/blog.wika.com\/en\/#website"},"primaryImageOfPage":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#primaryimage"},"image":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#primaryimage"},"thumbnailUrl":"https:\/\/blog.wika.com\/en\/files\/2016\/04\/plc.jpg","datePublished":"2016-03-31T08:00:10+00:00","dateModified":"2021-10-11T08:05:39+00:00","author":{"@id":"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343"},"description":"The construction of a traditional current loop for the capture of pressure sensor signals has its pitfalls.","breadcrumb":{"@id":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#breadcrumb"},"inLanguage":"en-GB","potentialAction":[{"@type":"ReadAction","target":["https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/"]}]},{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#primaryimage","url":"https:\/\/blog.wika.com\/en\/files\/2016\/04\/plc.jpg","contentUrl":"https:\/\/blog.wika.com\/en\/files\/2016\/04\/plc.jpg","width":838,"height":471,"caption":"Integration of pressure sensors into the PLC"},{"@type":"BreadcrumbList","@id":"https:\/\/blog.wika.com\/en\/knowhow\/integration-of-pressure-sensors-into-the-plc\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/blog.wika.com\/en\/"},{"@type":"ListItem","position":2,"name":"Integration of pressure sensors into the PLC"}]},{"@type":"WebSite","@id":"https:\/\/blog.wika.com\/en\/#website","url":"https:\/\/blog.wika.com\/en\/","name":"WIKA blog","description":"Our blog offers many interesting articles on pressure, temperature, level, force, flow measurement calibration technology and provides insights into the WIKA Group.","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/blog.wika.com\/en\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-GB"},{"@type":"Person","@id":"https:\/\/blog.wika.com\/en\/#\/schema\/person\/2315f4f9379074507a283fc8cf51a343","name":"Stefan Heusel","image":{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png","url":"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png","contentUrl":"https:\/\/blog.wika.com\/en\/files\/2015\/03\/default_avatar-140x140.png","caption":"Stefan Heusel"},"url":"https:\/\/blog.wika.com\/en\/author\/snhl\/"}]}},"_links":{"self":[{"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/posts\/6924","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/users\/16"}],"replies":[{"embeddable":true,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/comments?post=6924"}],"version-history":[{"count":17,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/posts\/6924\/revisions"}],"predecessor-version":[{"id":12383,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/posts\/6924\/revisions\/12383"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/media\/7043"}],"wp:attachment":[{"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/media?parent=6924"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/categories?post=6924"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/blog.wika.com\/en\/wp-json\/wp\/v2\/tags?post=6924"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}